Troubleshooting & Operational Runbook
This operational runbook provides field diagnostic playbooks for electricians, installers, and remote support engineers troubleshooting the Aslandi Edge Converter.
1. Quick Incident Diagnostic Matrix
| Symptom | Probable Cause | Diagnostic Check | Remediation Action |
|---|---|---|---|
| Status LED blinks rapid RED | Power supply voltage drop below $4.75\text{ V}$ | Measure 5V rail with DMM | Verify power supply capacity ($5\text{V} / 2\text{A}$ minimum required). |
| No meters discovered in scan | Inverted A/B RS-485 polarity or wrong baud | Check voltage difference ($V_A - V_B \approx 200\text{ mV}$) | Swap $A$ and $B$ differential wires; ensure $120\ \Omega$ termination jumper is set. |
| Status LED blinks YELLOW | MicroSD card unseated or corrupted block | Check /api/status SD alarm flag | Re-seat card or format with FAT32/exFAT; firmware will initialize fresh mirrors. |
Cloud connection fails (DISCONNECTED) | mTLS handshake rejection or clock drift | Check RTC time in /api/time | Ensure converter date/time is valid; expired or wrong clock will fail TLS handshake. |
Cannot access 192.168.4.1 | SoftAP timed out (15-min limit) | Search for Wi-Fi SSID | Press the service button on converter to re-enable SoftAP mode for 15 minutes. |
LOGIN_LOCKOUT on web panel | 5 consecutive invalid PIN attempts | Observe status screen | Wait 15 minutes for security lockout timer to expire, then enter PIN from label. |
2. Deep-Dive Field Diagnostics
A. RS-485 Communication Loss
- Check Bus Voltage: When idle, the non-inverting terminal ($A$) should measure approximately $+2.5\text{ V}$ to $+3.3\text{ V}$, and inverting terminal ($B$) should measure $+1.5\text{ V}$ to $+2.5\text{ V}$.
- Termination Resistors: A long RS-485 daisy chain requires exactly two $120\ \Omega$ termination resistors — one at the converter and one at the final physical meter on the bus. Unpowered resistance between $A$ and $B$ across the bus should measure approximately $60\ \Omega$.
- Meter Slave Address Conflict: Ensure each meter on Channel 0 has a unique slave ID in the range
1to50.
B. MicroSD Card Recovery Procedure
If the converter flags ALARM_SD_CORRUPTED:
- Power down the converter.
- Remove the microSD card and insert it into a diagnostic PC.
- If partition is unreadable, reformat the card using the official SD Card Formatter tool.
- Re-insert the card and power on the converter. The firmware automatically detects the clean card, generates fresh encryption sectors, and resumes mirroring.
3. Hardware Factory Reset
To restore the converter to factory default settings (clearing Wi-Fi credentials and resetting to SoftAP mode):
flowchart LR
Step1["1. Power off converter"] --> Step2["2. Hold down service button"]
Step2 --> Step3["3. Apply power while holding button"]
Step3 --> Step4["4. Keep button pressed for 10 seconds until LED blinks WHITE"]
Step4 --> Step5["5. Release button; configuration wiped & device reboots into SoftAP mode"]